Container connectivity
Jonny,
please check with a potential contractor for electricity connection on site what type of cable they would recommend to connect the transformer to the container.
The power of container is 400 kW, there is one 630A circuit breaker installed inside the container. The distance between transformer and container will be 20 meters.
please check with a potential contractor for electricity connection on site what type of cable they would recommend to connect the transformer to the container.
The power of container is 400 kW, there is one 630A circuit breaker installed inside the container. The distance between transformer and container will be 20 meters.
Comments & Events
They estimate Three 5g 240 Alu cables
Please ask for a link this cable on any web site with description
http://media.draka.no/2015/06/PFSP-1kV-Al.pdf